2009年1月19日星期一

Current transformer

A current transformer (CT) is a type of instrument transformer designed to provide a current in its secondary winding proportional to the alternating current flowing in its primary. They are commonly used in metering and protective relaying in the electrical power industry where they facilitate the safe measurement of large currents, often in the presence of high voltages. The current transformer safely isolates measurement and control circuitry from the high voltages typically present on the circuit being measured.


Design
Depending on the ultimate clients requirement, there are two main standards to which current transformers are designed. IEC 60044-1 (BSEN 60044-1) & IEEE C57.13 (ANSI), although the Canadian & Australian standards are also recognised.

The most common design of CT consists of a length of wire wrapped many times around a silicon steel ring passed over the circuit being measured. The CT's primary circuit therefore consists of a single 'turn' of conductor, with a secondary of many hundreds of turns.

The CT acts as a constant-current series device with an apparent power burden a fraction of that of the high voltage primary circuit. Hence the primary circuit is largely unaffected by the insertion of the CT.

Common secondaries are 1 or 5 amperes. For example, a 4000:5 CT would provide an output current of 5 amperes when the primary was passing 4000 amperes. The secondary winding can be single ratio or multi ratio, with five taps being common for multi ratio CTs.

Usage
Current transformers are used extensively for measuring current and monitoring the operation of the power grid. The CT is typically described by its current ratio from primary to secondary. Often, multiple CTs are installed as a "stack" for various uses (for example, protection devices and revenue metering may use separate CTs). Similarly potential transformers are used for measuring voltage and monitoring the operation of the power grid.

Shapes and sizes can vary depending on the end user or switchgear manufacture. Typical examples of low voltage single ratio metering current transformers are either ring type or plastic moulded case.

Connections
For IEC (BSEN) typically, the secondary connection points are labeled as 1S1, 1S2, 2S1, 2S2 etc for multi cores CT's or S1, S2, etc for single core single ratio CT's, or in the ANSI/IEEE standard areas, X1...X5, Y1...Y5, and so on. The multi ratio CTs are typically used for current matching in current differential protective relaying applications.

For a three-stacked CT application, the secondary winding connection points are typically labelled Xn, Yn, Zn.

Safety precautions
Care must be taken that the secondary of a current transformer is not disconnected from its load while current is flowing in the primary, as the transformer secondary will attempt to continue driving current across the effectively infinite impedance. This will produce a high voltage across the open secondary (into the range of several kilovolts in some cases), which may cause arcing. The high voltage produced will compromise operator and equipment safety and permanently affect the accuracy of the transformer.

Accuracy
The accuracy of a CT is directly related to a number of factors including:

Burden
Burden class/saturation class
Rating factor
Load
External electromagnetic fields
Temperature and
Physical configuration.
For the IEC standard, accuracy classes for various types of measurement are set out in BSEN /IEC 60044-1, class 0.1, 0.2s, 0.2, 0.5, 0.5s, 1 & 3. It will be seen that the class designation is an approximate measure of the accuracy, e.g., class 1 current transformers have ratio error within 1% of rated current class 0.5 within a ratio error of 0.5% etc. Phase difference is important when power measurements are involved, i.e. when using wattmeter's, kilowatt-hour meters, VAr meters and Power Factor meters.

Burden
The burden in a CT metering circuit is essentially the amount of impedance (largely resistive) present. Typical burden ratings for IEC CTs are 1.5VA, 3VA, 5VA, 10VA, 15VA, 20VA, 30VA, 45VA & 60VA with ANSI/IEEE B-0.1, B-0.2, B-0.5, B-1.0, B-2.0 and B-4.0. This means a CT with a burden rating of B-0.2 can tolerate up to 0.2 Ω of impedance in the metering circuit before its output current is no longer a fixed ratio to the primary current. Items that contribute to the burden of a current measurement circuit are switch blocks meters and intermediate conductors. The most common source of excess burden in a current measurement circuit is the conductor between the meter and the CT. Often, substation meters are located significant distances from the meter cabinets and the excessive length of small gauge conductor creates a large resistance. This problem can be solved by using CT with 1 ampere secondaries which will produce less voltage drop between a CT and its metering devices (used for remote measurement).


Burden class IEEE/ANSI (Also called Knee-point Voltage)
This is the voltage at which a CT becomes saturated. When a CT becomes saturated it can no longer transform current. An example of this rating would be C200, C800 etc... This means that the CT will saturate near 200 Volts or 800 Volts respectively.


Rating factor
Rating factor is a factor by which the nominal full load current of a CT can be multiplied to determine its absolute maximum measurable primary current. Conversely, the minimum primary current a CT can accurately measure is "light load," or 10% of the nominal current (there are, however, special CTs designed to measure accurately currents as small as 2% of the nominal current). The rating factor of a CT is largely dependent upon ambient temperature. Most CTs have rating factors for 35 degrees Celsius and 55 degrees Celsius. It is important to be mindful of ambient temperatures and resultant rating factors when CTs are installed inside pad-mounted transformers or poorly ventilated mechanical rooms. Recently, manufacturers have been moving towards lower nominal primary currents with greater rating factors. This is made possible by the development of more efficient ferrites and their corresponding hysteresis curves. This is a distinct advantage over previous CTs because it increases their range of accuracy, since the CTs are most accurate between their rated current and rating factor.


Physical configuration
Physical CT configuration is another important factor in reliable CT accuracy. While all electrical engineers are quite comfortable with Gauss' Law, there are some issues when attempting to apply theory to the real world. When conductors passing through a CT are not centered in the circular (or oval) void, slight inaccuracies may occur. It is important to center primary conductors as they pass through CTs to promote the greatest level of CT accuracy.

In power systems applications, many CT configurations bypass this limitation by either being custom designed to slip around the bushing of a high-voltage transformer or circuit breaker, which automatically centers the conductor inside the CT window, or by having the primary turn permanently fixed inside the CT housing and accessible only by means of external terminals.


Special designs
Specially constructed wideband current transformers are also used (usually with an oscilloscope) to measure waveforms of high frequency or pulsed currents within pulsed power systems. One type of specially constructed wideband transformer provides a voltage output that is proportional to the measured current. Another type (called a Rogowski coil) requires an external integrator in order to provide a voltage output that is proportional to the measured current. Unlike CTs used for power circuitry, wideband CTs are rated in output volts per ampere of primary current.


Three Phase Generator


Toroidal Power Transformer


oil immersed transformer


medical ozone generator


Audio Output Transformer


Surface Mount Transformer


Single Phase Transformer


Portable Diesel Generator


Cummins Generator Set


current sense transformer


common mode inductor


neon light transformers


Gas Generator Set


heavy duty generator


h f transformer


halogen light transformer


air ozone generator


induction heating generator


membrane nitrogen generator


welder and generator


perkins diesel generator

没有评论:

发表评论